8 It protects the valves and prevents water from dripping. The unit has 3 mins delay between continuously ON/OFF operations. Outdoor unit
93. Dimension 3.1 Indoor Units Model W H D KSIL009-H116 790 (31.1 in) 265 (10.4 in) 198 (7.8 in) KSIL009-H119 KSIL012-H216 K
10 For the other models
11 3.2 Outdoor Units More than 30cmMore than 60cmMore than 70cmMore than 30cmMore than 60cm(Service space)Fence orobstacles
12 4. Refrigerant Cycle Diagram For cooling only models: INDOOROUTDOORLIQUID SIDEGAS SIDEHEATEXCHANGE(EVAPORATOR)HEATEXCHANGE(CONDENSER)CO
13For heat pump models: INDOOROUTDOORLIQUID SIDEGAS SIDEHEATEXCHANGE(EVAPORATOR)HEATEXCHANGE(CONDENSER)COMPRESSOR2-WAY VALVE3-WAY VALVECHE
145. Wiring Diagram 5.1 Indoor Units KSIL009-H116, KSIL012-H216, KSIL012-H219 KSIL009-H119
15KSIL018-H216, KSIL018-H219, KSIL024-H216
16KSIL009-H119 KSIL012-H119
175.2 Outdoor Units KSIL009-H116; KSIL009-H119;
CONTENTS 1. Precaution ...
18KSIL012-H219 KSIL018-H216
19KSIL018-H219 KSIL024-H216
20 KSIL024-H216
216. Installation details 6.1 Wrench torque sheet for installation Outside diameter Torque Additional tightening torque mm inch N.cm
226.2 Connecting the cables The power cord of connect should be selected according to the following specifications sheet. Rated current of
236.3 Pipe length and the elevation The pipe length and refrigerant amount: Model Connective pipe length Air purging method Additional a
246.4 Installation for the first time Air and moisture in the refrigerant system have undesirable effects as below: ● Pressure in the s
25the meter does not indicate -0.1Mpa after pumping 30 minutes, it should be pumped 20 minutes more. If the pressure can’t achieve -0.1Mpa
26Close the valve on the charging cylinder and discharge the refrigerant by loosening the flare nut on the 2-way valve approximately 45’ u
276).When the electronic scale displays the proper weight (refer to the table), disconnect the charge hose from the 3-way valve’s service
1 1. Precaution 1.1 Safety Precaution To prevent injury to the user or other people and property damage, the following instructions must be follo
286).When the electronic scale displays the proper weight (refer to the gauge and the pressure of the low side), disconnect the charge hos
295). Operate the air conditioner at the cooling cycle and stop it when the gauge indicates 0.1MPa. 6). Set the 3-way valve to the closed
30Close the valve on the charging cylinder and discharge the refrigerant by loosening the flare nut on the 2-way valve approximately 45’ u
312. Refrigerant charging Procedure: 1). Connect the charge hose to the charging cylinder, open the 2-way valve and the 3-way valve Conne
32Use torque wrench to tighten the service port cap to a torque of 18N.m. Be sure to check for gas leakage.
337. Operation characteristics Temperature Mode Cooling operation Heating opera
348. Electronic function 8.1 Abbreviation T1: Indoor room temperature T2: Coil temperature of evaporator T3: Coil temperature of
35 DEFROST indication lamp (For cooling & heating models only): Lights up when the air conditioner starts defrosting automatically o
36When the unit starts up, the louver will be active immediately and the indoor fan will open 10s later. If the unit runs in heating mode,
378.4.2.1 Compressor running rules: The operation frequency of compressor after starting submits to following rule. 4543403830282220Fmax=F
2condenser and evaporator. For installation, always contact the dealer or an Authorized service center. There is risk of fire, electric
38F: Keep the current frequency. G: Decrease the frequency to the lower level until to F1. H: Run at F1 for 1h.(if T1-Ts<-4 ºF, the com
3943HighLow1Medium1.5 8.4.2.4 Condenser high temperature T3 protection. ---131 ºF <T3<140 ºF, the compressor frequency will decrease
408.4.3 Heating Mode 8.4.3.1 Compressor running rules: The maximum operation frequency of the compressor after starting submits to the fol
41+5.0+4.5+3.5+3.0+2.5+2.0+1.5+1.0HGHFEDCBA+0.5 While Temp. zone A B C D E F G Frequency F10 F9 F8 F7 F5 F3 F1 ∆T=0 as factory setting.
42I3HEATI2HEATI1HEATOff DecreaseHoldResume Off: Compressor stops. Decrease: Decrease the running frequency to the lower level.
438.4.3.3 Indoor fan running rules: 4438373433SettingLowBreezeOff17 If the compressor stops caused by the room temperature rising, the ind
44The units run with T3< 37 ºF for 80 minutes and T3 keeps lower than TCDI +35.6 ºF for more than 3 minutes. While TCDI=21 ºF. ----T4<3
45Defrosting action:::: For 18k, 24k models: Model FD FD1 KSIL018-H216 60 70 KSIL018-H219 90 100 KSIL024-H216
46For other models: 8.4.3.5 Evaporator coil temperature protection ----T2>TEH 35.6 ºF, the compressor running frequency decreases to t
47Indoor fan will run at auto fan of the relevant mode. The louver operates same as in relevant mode. If the machine switches mode between
3There is risk of explosion or fire. If strange sounds, or small or smoke comes from product. Turn the breaker off or disconnect the po
488.4.6.3 Operation rules: Forced cooling mode: The compressor runs at F2 frequency and indoor fan runs as breeze. After running for 30 mi
498.4.9 Auto-Restart function The indoor unit is equipped with auto-restart function, which is carried out through an auto-restar
509. Troubleshooting 9.1 Indoor Unit Error Display Display LED STATUS E0 EEPROM parameter error E1 Indoor / outdoor units communication
519.2 Diagnosis and Solution 9.2.1 EEPROM parameter error diagnosis and solution Shut off the power supply and turn on it 5s later The pr
529.2.2 Indoor unit and outdoor unit communication protection error diagnosis and solution No Yes Yes No Yes The unit does not work norm
539.2.3 Fan speed has been out of control diagnosis 9.2.4 Open or short circuit of temperature sensor diagnosis and solution Yes Repla
549.2.5 IGBT over-strong current protection diagnosis and solution 9.2.6 Over voltage or too low voltage protection diagnosis and solutio
559.2.8 Inverter compressor drive error diagnosis and solution 9.2.9 Zero crossing detection error This is alarm signal when the main chi
56Appendix: ℃ 10 11 12 13 14 15 16 F 48 50 52 54 56 58 60 ℃ 17 18 19 20 21 22 23 F 62 64 66 68 70 72 74 ℃ 24
Tel: (305)594-4972 Fax (305) 675-2212www.klimaire.com [email protected] NW 89 Place, Doral, FL 33172 - USAThe Klimaire logo is a registered
4 Keep level even when installing the product. It can avoid vibration of water leakage. Do not install the product where the noise or
5damage. Do not insert hands or other object through air inlet or outlet while the product is operated. There are sharp and moving part
62. Function Model Names of Indoor/Outdoor Units DC Inverter Capacity Model Indoor units Outdoor units 9K KSIL009-H216 KSIL009-H216 K
7 The louver can be set at the desired position or swing up and down automatically The function is usually used in rainy days in springti